How the cable is fixed to the pipe matters more than most installers expect. Poor fixing reduces heat transfer, damages the cable jacket, and creates loose sections that vibrate or sag. These are the attachment methods that work, and the mistakes that cause call-outs later.

1. Aluminium foil tape (with or without adhesive)

Aluminium tape improves thermal contact between the cable and the pipe and protects the jacket. It is the default for straight runs. Use adhesive-backed tape where the pipe is clean and dry; otherwise use non-adhesive tape with stainless steel ties at intervals.

2. Fibreglass tape

High-temperature resistant and cheap, but poor thermal contact and lower mechanical strength. Suitable for securing on hot pipes where aluminium tape adhesive would fail, but it should not be the only fixing on a vibrating line.

3. Stainless steel cable ties

Mechanical and durable, good for vertical runs and for holding cable in place above insulation. Tighten only enough to hold the cable — over-tightening crushes the cable and creates a hot spot or earth fault.

4. Plastic cable ties

Only for areas not exposed to UV, low temperature or chemicals, and only as a temporary or supplementary fixing. Most plastic ties become brittle and fail within a few winters outdoors.

5. Clips and channels

Useful for protecting cable on walkways and for routing across supports. Clips must match the cable diameter and must not compress the cable.

6. Spacing and routing rules

Keep the recommended fixing spacing (typically 30–50 cm on straight runs, closer on bends and vertical runs). Route the cable on the lower half of the pipe for horizontal lines and away from welds, sharp supports and hot surfaces. Leave expansion loops where the pipe moves.

7. What not to do

Why thermal contact matters

A cable that is loosely attached still produces heat, but much of it goes into the air gap instead of the pipe. The circuit then draws normal current and the pipe stays below design temperature — a problem that looks like a design error but is actually an installation error. Aluminium tape and correct spacing are the cheap fix.

MethodBest useWatch out
Aluminium tapeStraight runs, good thermal contactAdhesive fails on hot or wet pipes
Fibreglass tapeHigh temperature areasPoor thermal contact
Stainless tiesVertical runs, mechanical securityOver-tightening damages cable
Plastic tiesIndoor, temporaryUV and cold embrittlement
Clips/channelsWalkways, supportsMust match diameter, no compression

Installation specification needed?

Send the pipe list and cable types. We provide a fixing specification, spacing drawing and accessory list.