Heat Tracing for Refrigeration Plants
Industrial refrigeration plants using ammonia or CO2 have lines that must not freeze, must not lose temperature, and must not leak. Heat tracing there sits between process safety and mechanical integrity — and the refrigerant itself changes the design.
Where tracing is applied
- Defrost and drain lines: condensate and defrost water freezing on the floor or in drains.
- Cold-store floor and door heating: preventing frost heave and door freezing.
- Glycol and secondary refrigerant loops: freeze protection when idle.
- Ammonia pump and receiver lines: keeping oil and liquid moving; some sections must be kept warm, others must not.
- CO2 systems: high-pressure lines need care with heat input; low-temperature lines need insulation, not heating.
- Water and utility lines in plant rooms: standard freeze protection.
Design points
1. Know which lines must NOT be heated
Refrigerant liquid lines must not be warmed — that changes subcooling and can affect the system. The engineering task is to sort lines into "must heat", "must not heat" and "must insulate only". Getting this wrong is worse than doing nothing.
2. Ammonia is hazardous
Ammonia areas are classified; equipment must be certified for the zone gas group, and any heat source near ammonia lines must be designed for the leak scenario.
3. Frost heave and floors
Cold-store floors need a heater grid to prevent frost heave; that is a different product from line tracing, usually a constant-wattage cable designed for the slab.
4. Defrost water
Defrost water lines freeze quickly. Trace and insulate them, and slope to drain.
5. Insulation dominates energy
Refrigeration plants run continuously; poorly insulated traced lines waste energy all year.
6. Controls and alarms
Freeze protection here is usually not critical-path, but defrost and door systems directly affect operation. Alarms should reach whoever runs the plant.
Checklist
| Item | Confirm |
|---|---|
| Line classification | Must heat / must not heat / insulate only |
| Refrigerant | Ammonia or CO2, pressure class, temperature range |
| Area classification | Zone and gas group for ammonia areas |
| Floors | Frost heave protection design |
| Condensate | Defrost water tracing and drainage |
| Energy | Insulation specification, operating hours |
| Alarms | Door/defrost/line alarms to plant staff |
Common mistakes
- Tracing a refrigerant liquid line "for safety" and changing system performance.
- Certified cable with uncertified junction boxes in an ammonia area.
- No frost-heave protection under a freezer floor.
- Defrost drains left untraced and un-sloped.
- Energy ignored because "it's only freeze protection".