Heat Tracing Cable Termination: 6 Steps and Common Mistakes

INTAYE Technical Library · Jiangsu Intaye Electric Co., Ltd. · 2026-10-07

Terminations are the weakest point of every heat tracing circuit: most earth faults and low insulation resistance values come from a termination that was made badly or exposed to moisture. This is the practical procedure and the mistakes that cause failures.

Before you start

Six steps

1. Cut cleanly

Use a proper tool. A crushed or ragged cut damages the core and is hard to seal.

2. Strip the jacket to the correct length

Follow the kit drawing; too long exposes the core, too short leaves no room for the seal.

3. Remove the insulation without nicking the core

The most common cause of a later fault is a nick in the conductor or the PTC core.

4. Fit the seal and the end cap

Use the correct sealant and heat-shrink as specified; keep the bus wires separated and insulated. A poorly sealed end absorbs moisture and shows up as an earth fault weeks later.

5. Connect and strain-relieve

Terminate into the junction box with the correct glands, and ensure the cable is supported so the termination carries no mechanical load.

6. Test

Insulation resistance, continuity and (for self-regulating cable) correct resistance between bus wires. Record the values.

Common mistakes

MistakeTypical consequence
Nick in the core during strippingHot spot, then failure
Moisture inside the end capEarth fault after weeks
Wrong kit for the cable typeOverheating or poor seal
Bus wires not separatedShort circuit
Termination carrying cable weightCracked seal, water ingress
No test recordNo baseline for future comparison

Which terminations are most at risk

Outdoor terminations, washdown areas, underground and buried lines, and cold-climate installations where the cable is stiff and the sealant cures slowly. In these locations it is worth using a junction box rather than a bare end, and protecting the entry from water.

Records

Record the circuit number, cable type, termination date, insulation resistance and the installer. This record is what lets a maintenance team find a fault in minutes instead of hours.

Termination or installation support?

Send the cable type and site conditions. We provide termination kits, procedures and on-site guidance.

Request Support