Heat tracing faults are usually diagnosed in the wrong order. Teams replace the controller first, then the cable, then the thermostat, and only find the real cause after several trips. This guide lists eight faults in the order they should be checked, based on field service reports.

Start with measurement, not replacement

Before touching anything, record three values per circuit: supply voltage, operating current and insulation resistance to earth. Compare them with the commissioning record. Most faults declare themselves in one of those three numbers.

8 common faults

1. The circuit trips at the breaker on cold start

Self-regulating cable draws a higher inrush current when cold. If the breaker is marginal, it trips only on the first cold morning. Check the manufacturer's cold-start current, not the steady-state current.

2. Current is lower than design but the cable is warm

Usually a damaged bus wire or a partly failed section: the circuit still draws some current but less than expected. Measure resistance at both ends to localise the failure.

3. No current at all

Check the isolator, the MCB and the controller output in that order. A thermostat stuck open and a blown fuse look identical from the panel. Verify with a clamp meter at the cable gland.

4. Earth leakage trips randomly

Moisture in a junction box or a nicked cable sheath. Disconnect sections one by one and measure insulation resistance of each section; do not simply raise the leakage setting.

5. One section stays cold while the rest works

Series-connected constant wattage circuits fail by a single break: everything downstream stops. Locate the break by measuring resistance from each end; the ratio indicates the distance to the fault.

6. Temperature overshoots the set point

Sensor placement, not controller tuning. If the sensor is not in good thermal contact with the pipe, the controller keeps heating after the pipe is already at temperature.

7. Alarms do not reach anyone

Local lamps are not alarms. Confirm the signal path from the panel to the DCS or the on-call phone, and test it with a simulated fault.

8. Repeat failures in the same location

Look for mechanical damage: scaffolding clamps, foot traffic on cladding, hot work nearby, or a cable route that crosses a hot surface. Replacing the cable without fixing the cause reproduces the fault.

A simple diagnostic sequence

Voltage at panel → voltage at junction box → insulation resistance → operating current → temperature reading → alarm path. Nine out of ten faults are identified within this sequence before any component is replaced.

Troubleshooting a specific circuit?

Send the cable type, circuit length, measured resistance and current. We return a fault analysis and replacement recommendation within 24 hours.